HIMA F3 AIO 8/4 01 | Safety-Related Controller

HIMA F3 AIO 8/4 01 | Safety-Related Controller

Brand: HIMA

Product ID: F3 AIO 8/4 01

Condition: New / used

Terms of payment: Paypal、T/T 、Western Union

Category:

Description

The safety-related F3 AIO 8/4 01 remote I/O is a compact system in a metal enclosure with 8 digital inputs, 8 digital DO+ outputs (L- ground), 2 digital DO-outputs (S+ ground) and 2 pulsed outputs. The digital outputs DO4+, DO8+, DO4- and DO8- can also be connected as two-pole connections.

The remote I/O is available in a model variant for SILworX and a model variant for ELOP II Factory, see Chapter 3.2. All variants are described in this manual.


The remote I/O serves to extend the I/O level of HIMax and HIMatrix controllers, and is connected to them via safeethernet. The remote I/O itself is not able to run a user program.

The HIMatrix remote I/Os are not multi-master capable.

The remote I/O is suitable for mounting in Ex-zone 2, see Chapter 4.1.4.

F3 AIO 84 01 (3).jpg

The device has been certified by the TÜV for safety-related applications up to SIL 3 (IEC 61508, IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1). Further safety standards, application standards and test standards are specified in the certificate available on the HIMA website.

Safety Function

The remote I/O is equipped with safety-related digital inputs and outputs. The input values on the inputs are safely transmitted to the connected controller viasafeethernet. The outputs are safely assigned their values by the connected controller via safeethernet.

Safety-Related Digital Inputs

The remote I/O is equipped with 20 digital inputs. The state (HIGH, LOW) of each input is signaled by an individual LED. Mechanical contacts without own power supply or signal power source can be connected to the inputs. Potential-free mechanical contacts without own power supply are fed via an internal short-circuit-proof 24 V power source (LS+). Each of them supply a group of 4 mechanical contacts. Figure 1 shows how the connection is performed. With signal voltage sources, the corresponding ground must be connected to the input (L-)

F3 AIO 84 01 (2).jpg

Main brands include: ABB, Bailey, GE, FOXBORO, Invensys TRICONEX, Bentley BENTLY, A-B Rockwell, EMERSON EMERSON, B&R, MOTOROLA, FUANC, REXROTH, KUKA, HONEYWELL, NI, DEIF, Yokogawa, WOODWARD WOODWARD, Ryan, SCHNEIDER SCHNEIDER, Yaskawa, MOOG, EPRO, PROSOFT and other major brands

 

Related Products

HIMA F6214HIMA F8627
HIMA F6215HIMA F3331
HIMA F6217HIMA F3238
HIMA F6706HIMA F3240
HIMA F7126HIMA F5203
HIMA F7553HIMA F5220
HIMA F8621AHIMA F6208
HIMA F8627XHIMA F6216

B.jpg

【 Disclaimer 】 We sell new products and discontinued products, independent channels to buy such special products. Guizhou Yuanmiao Automation Equipment Co., Ltd. is not an authorized distributor, dealer or representative of the products featured on this website. All product names/product images, trademarks, brands and microlabels used on this Website are the property of their respective owners. Descriptions, depictions or sales of products with such names/images, trademarks, brands and logos are for identification purposes only and do not imply any association or authorization with any rights holder. This article is from the official website of Guizhou Yuanmiao Automation Equipment Co., LTD. Please attach this link:http://www.ymdcs.com/HIMA/